'G' Series
Blower(s) shall be
belt driven, forward curve, DWDI with resilient mounted ball bearings having a
minimum L50 (average) life of 200,000 hours. Blower shall be
fabricated of galvanized steel. Blower wheel shall be fabricated of galvanized steel with
hook and slot type construction. Bearings
shall be ball bearing, permanently lubricated, resilient mounted in a 3-arm
bracket. Shaft shall be keywayed at each end.
Blower(s) shall be
Delhi Industries Inc., 'G' Series.
www.delhi-industries.com
'200' & '200-2' Series Duct Blowers
(Indoor Applications)
In-line
Duct Blower(s) shall be constructed of cold rolled steel with corrosion
resistant, high solids, baked enamel finish. Blower motor and drive access shall
be provided on both sides through removable panels. Blowers shall be belt drive,
forward curved, DWDI with resilient mounted, permanently lubricated, ball
bearings having a minimum L50 (average)
life of 200,000 hours. Shaft shall be keywayed at both ends.
(Optional - Cabinets shall be insulated with 1/2" thick fiberglass
insulation.)
Duct blower(s) shall be
licensed to bear the AMCA seal for Air and Sound Performance and be Listed UL
705.
Motor shall be continuous duty, permanently lubricated, ball bearing with a 1.15
service factor. Electrical
characteristics and features per schedule.
Drives are to be selected for 150% of driven
horsepower. Blower pulley shall be fixed, machined, cast iron. Motor pulley
shall be cast iron, variable speed.
Duct Blower(s) shall be Delhi Industries Inc., '200' or '200-2' Series. www.delhi-industries.com
'9200' & '9200-2' Series Duct Blowers
(Indoor or Outdoor Applications)
In-line
Duct Blower(s) shall be constructed of galvanized steel with corrosion
resistant, high solids, baked enamel finish and be insulated with 1/2" fibreglass
insulation. Blower motor and drive access shall be provided on both sides
through removable panels. Blower shall be belt drive, forward curved, DWDI with
ball bearings having a minimum L50
(average) life of 200,000 hours. Shaft shall be keywayed at both ends.
Duct blower(s) shall be
licensed to bear the AMCA seal for Air and Sound Performance and be Listed UL
705.
Motor shall be
continuous duty, permanently lubricated, ball bearing with a 1.15 service factor
and be rated for continuous duty. Electrical
characteristics and features as per schedule.
Drives are to be selected for 150% of driven
horsepower. Blower pulley shall be fixed, machined, cast iron. Motor pulley
shall be cast iron, variable speed.
Duct Blower(s) shall be Delhi Industries Inc.,
'9200' or '9200-2' Series. www.delhi-industries.com
'9200VIB' Series Duct Blowers
(Indoor or Outdoor Applications)
In-line
Duct Blower(s) shall be constructed of galvanized steel with corrosion
resistant, high solids, baked enamel finish and be insulated with 1/2" fibreglass insulation. Blower,
motor and drive access shall be provided on both sides through removable panels.
Blower shall be complete with internally mounted spring vibration isolators. The
blower(s) shall be belt driven, forward curved, DWDI, with ball bearings having
a minimum L50 (average)
life of 200,000 hours. Shaft shall be keywayed at both ends.
Duct blower(s) shall be
licensed to bear the AMCA seal for Air and Sound Performance and be Listed UL
705.
Motor(s) shall be
continuous duty, permanently lubricated, ball bearing with a 1.15 service
factor. Electrical characteristics and features per schedule.
Drives are to be
selected for 150% of driven horsepower. Blower pulley(s) shall be fixed,
machined, cast iron. Motor pulley(s) shall be cast iron, variable speed.
Duct Blower(s) shall be Delhi Industries Inc.,
'9200VIB' Series.
www.delhi-industries.com
'F200' Filter Section
(For '200', '9200' & '9200VIB' Duct Blowers)
Filter
Section(s) shall be fabricated of cold rolled steel with corrosion resistant, high solids,
baked enamel paint finish and insulated with 1/2" fibreglass
insulation. The filter shall be 1" thick, permanent, washable, aluminums
mesh. Filter rack shall have provision to accommodate 2" thick filters.
Removable end panel shall provide service access.
Filter Section(s) shall
be Delhi Industries Inc., 'F200' or 'F9220' Series www.delhi-industries.com
'HC' Hot Water Heating Coil
Hot Water Heating Coil(s) shall be enclosed in a cold rolled steel, insulated
cabinet with corrosion resistant, baked green enamel paint finish. The
coil shall consist of 2
rows of 3/8" copper tubes expanded on to aluminum fins at a density of 12
fins per inch. The coil shall be of
lead free construction and be suitable for use with potable water systems.
Hot Water Coil(s) shall be Delhi Industries Inc., 'HC'
Series www.delhi-industries.com
'CW' Chilled Water
Cooling Coil
Chilled Water Cooling
Coil(s) shall be enclosed in a cold rolled steel, insulated cabinet with
corrosion resistant, baked
green enamel paint finish. The coil shall consist of 4 rows of 3/8" copper
tubes expanded on to aluminum fins at a density of 12 fins per inch.
The drain pan shall be of corrosion resistant galvanized steel and sloped
to ensure free condensate drainage.
Chilled
Water Coil(s) shall be Delhi Industries Inc., 'CW' Series www.delhi-industries.com
'H9200' Intake Filter
Hood
Intake Hood(s) shall be
fabricated of galvanized steel with corrosion resistant, baked green
enamel paint
finish. Intake shall be sloped to prevent the entrainment of rain and contain
integral 1 in. thick aluminum mesh filters that can be serviced through a
removable end cap. For 20"
models (9220 & 9220-VIB) the intake shall be screened and require a separate
model F9220 filter section with sloped filter bank of 1” aluminums filters.
Intake Filter Hood(s)
shall be Delhi Industries Inc., 'H9200' Series www.delhi-industries.com
'300' Series Exhauster
Curb Mounted
Exhauster(s) shall be fabricated of galvanized steel with corrosion resistant, high solids baked
enamel finish. A removable top panel shall provide access
to the integral blower, motor & drives. Blower shall be belt driven, forward
curved with resilient mounted, permanently lubricated, ball bearings having a
minimum L50 (average) life of 200,000 hours. Shaft shall be keywayed
at both ends.
Exhauster(s) shall be
licensed to bear the AMCA seal for Air and Sound Performance and be listed
UL705.
Motor shall be
continuous duty, permanently lubricated, ball bearing with a 1.15 service
factor. Electrical characteristics and features per schedule.
Drives shall be
selected for 150% of driven horsepower. Blower pulley(s) shall be fixed,
machined cast iron. Motor pulley(s) shall be cast iron, variable speed.
Exhauster(s) shall be
Delhi Industries Inc., '300' Series www.delhi-industries.com
'400' Series Framed
Utility Blower
Framed (SWSI)
Utility Blower(s) shall be forward curved belt driven. Blower housing shall be
galvanized steel.
Angled steel reinforcing frames to provide multiple motor mounting options for 4
discharge positions. Bearings (models 407 to 418) shall be permanently
lubricated, resilient mounted, ball bearing. Models 420 to 425 shall have
self-aligning pillow block bearings with provision for field re-lubrication.
All bearings shall have a minimum L50 (average) life of
200,000 hours. Shaft shall be keywayed.
(Optional): - Belt Guard: Blower shall have a factory
supplied belt guard.
Framed Utility Blower(s) shall be Delhi Industries Inc., '400' Series. www.delhi-industries.com
'600' Series Utility
Blower (Vent Set)
Forward Curved
Utility Blower(s) shall be AMCA Arrangement 10, (SWSI). Centrifugal FC wheel
shall be, fabricated of galvanized steel. Blower housing shall be fabricated of
cold rolled steel. Bearing and motor platform support shall be fabricated from
angle iron and be complete with sliding motor platform for belt tension
adjustment. Provide galvanized motor compartment cover. Finish shall be
corrosion resistant, high solids, baked enamel paint. Bearings shall be pillow
block, self-aligning, ball bearing, with a minimum L50 (average) life
200,000 hours. Shaft shall be keywayed.
Each blower shall be
licensed to bear the AMCA Certified Ratings Seal for Air Performance.
Motors shall be
continuous duty with permanently lubricated ball bearings. Electrical
characteristics and enclosure per schedule. Drives are to be selected for 150%
of driven horsepower. Blower pulley(s) shall be fixed, machined, cast iron.
Motor pulley(s) shall be cast iron, variable speed.
(Optional): Utility Blower(s)
are to be provided with (select as required)
Inlet
screen,
outlet screen,
back draft damper,
Clean-out
access panel,
drain fitting,
heat slinger,
Shaft
seal,
Heresite
corrosion resistant coating on air stream surfaces.
Utility Blower(s) shall be Delhi Industries Inc., '600'
Series. www.delhi-industries.com
'700' Series Fresh Air
Supply Unit
Fresh Air Supply
Fan shall be curb mounted with filtered intakes on four sides. Cabinets shall be
fabricated of galvanized steel with corrosion resistant, high solids, baked
enamel finish. Blowers shall be belt drive, FC (forward curved), DWDI with
resilient mounted ball bearings having a minimum L50
(average) life of 200,000 hours. Shafts shall be keywayed at both ends.
A removable, latched, top panel shall provide for service access to both
the filters and motor /blower assembly. Bearings shall be resilient mount,
permanently lubricated, ball bearing, with a minimum L50 (average)
life of 200,000 hours. Filter shall be aluminum, 1" thick, permanent,
washable.
Fresh Air Supply Unit
shall be licensed to bear the AMCA seal for Air and Sound Performance and be
listed UL 705.
Motor shall be
continuous duty, permanently lubricated, ball bearing with a 1.15 service
factor. Electrical characteristics and enclosure per schedule. Drives are to be
selected for 150% of driven horsepower. Blower pulley shall be fixed, machined,
cast iron. Motor pulleys shall be cast iron, variable speed.
Fresh Air Supply Unit(s) shall be Delhi Industries Inc., '700' Series. www.delhi-industries.com
'800' Series Blowers
Blower(s) shall be
belt driven double-width, double inlet (DWDI) with forward curved
(FC) wheel fabricated of galvanized steel with hook and slot
construction. Bearings shall be permanently lubricated, ball bearing, with a
minimum L50 (average) life of 200,000 hours, resilient mounted in a
3-arm bracket. Blower housings shall be fabricated of cold rolled steel and
reinforced with angular steel frames. Finish shall be corrosion resistant, high
solids, baked green enamel. Shaft shall be keywayed at each end.
(Optional) - Belt Guard:
Blower shall have a factory supplied belt guard.
Blower(s) shall be
Delhi Industries Inc., '800' Series. www.delhi-industries.com
'900' Series Blowers
Blower(s) shall be
belt driven double-width, double inlet (DWDI) with forward curved (FC) wheels.
Housings shall be fabricated galvanized steel and reinforced with angular steel side
frames. Finish shall be corrosion
resistant, high solids, baked green enamel.
Bearings shall be self-aligning, pillow block ball bearing, with a
minimum L50 (average) life of 200,000 hours with provision for
re-lubrication. Shafts shall be keywayed at both ends.
(Optional): - Pivoting base
motor platform.
Blower(s) shall be
Delhi Industries Inc., '900' Series www.delhi-industries.com
'SIS' Series Side Intake,
Fresh Air Supply Unit
Filtered Fresh Air
Supply Unit(s) shall be curb mounted with single side intake and be fabricated
of galvanized steel with corrosion resistant, high solids, baked green enamel
finish. Blower shall be belt drive, FC (forward curved), DWDI with resilient
mounted ball bearings (pillow block self aligning bearing for SIS-20) having a
minimum L50 (average)
life of 200,000 hours. A removable, latched, top panel shall provide for service
access to the motor/blower assembly. Filters
shall be 1" thick, aluminum mesh, permanent, washable and be serviceable
through a removable end cap. For model SIS-20 only, the intake shall be screened
and require a separate model F9220 filter assembly.
Fresh Air Supply
Unit(s) shall be licensed to bear the AMCA seal for Air and Sound Performance
and be listed UL 705.
Motor shall be continuous duty, permanently lubricated,
ball bearing, with a 1.15 service factor. Electrical characteristics and
enclosure per schedule. Drives are to be selected for 150% of driven horsepower.
Blower pulleys shall be fixed, machined, cast iron. Motor Pulleys shall be cast
iron, variable speed.
Fresh Air Supply Unit(s) shall be Delhi Industries Inc., 'SIS' Series.
www.delhi-industries.com
'BI' Series Utility
Blower (Vent Set)
Utility Blowers shall be AMCA
Arrangement 10, Class I, Backward Inclined (BI). Blower housing shall be
fabricated of cold rolled steel. Bearing and motor platform support shall be
fabricated from angle iron and be complete with sliding motor platform for belt
tension adjustment. Provide galvanized, weather resistant, motor compartment
cover. Finish shall be corrosion resistant, high solids baked enamel paint.
Shaft shall be keywayed. Wheels
shall be of heavy gauge steel; bearings shall be pillow block, self- aligning,
with provision for field lubrication and have a minimum L50 (average)
life of 200,000 hours.
Utility Blower(s) shall
be licensed to bear the AMCA seal for Air Performance and be listed UL
705.
Motor shall be continuous duty, permanently lubricated, ball bearing with a 1.15
service factor. Electrical characteristics and enclosure per schedule. Drives
are to be selected for 150% of driven horsepower. Blower pulleys shall be fixed,
machined, cast iron. Motor pulleys shall be cast iron, variable speed.
(Optional): Blowers are
to be provided with (select as required)
Spark
Resistant AMCA Type 'B' construction with aluminum wheel.
Inlet
screen,
outlet screen,
back draft damper,
Clean-out
access panel,
drain fitting,
heat slinger,
Shaft
seal,
Heresite
corrosion resistant coating on air stream surfaces.
Utility blowers shall
be Delhi Industries Inc., ‘BI” Series www.delhi-industries.com
'BI' Series Restaurant
Exhauster
Restaurant Exhauster(s) shall be AMCA Arrangement
10, Class I, Backward Inclined (BI). Blower housing shall be fabricated of cold
rolled steel. Bearing and motor platform support shall be fabricated from angle
iron and be complete with sliding motor platform for belt tension adjustment.
Provide galvanized, weather resistant, motor compartment cover. Finish shall be
corrosion resistant, high solids, baked enamel paint. Shaft shall be keywayed.
Wheel shall be of heavy gauge steel; bearings shall be pillow block,
self- aligning, with provision for field lubrication and have a minimum L50
(average) life of 200,000. Exhauster
shall have upblast discharge with continuously welded 16 gauges or heavier
housing, 2" drain, bolted and gasketed access panel.
Exhauster(s) shall be
Listed UL 762 ‘Power Roof Ventilators for Restaurant Exhaust Appliances’,
Listed UL
705 and be licensed to bear the AMCA seal for Air Performance.
Restaurant Exhauster shall be Delhi Industries Inc.,
'BI-RM' Series www.delhi-industries.com
'BIDI' Series Blowers
Blower(s) shall
be DWDI, AMCA Arrangement 3, and Class I. Blower housing shall be fabricated of
cold rolled steel, reinforced with ‘U’ channel steel side frames. Finish
shall be corrosion resistant, high solids, baked enamel. Blower wheels shall be
heavy gauge, backward inclined and dynamically balanced in 2 planes. Bearings
shall be self-aligning, pillow block, ball bearing with a minimum L50
(average) life of 200,000 hours and provision for re-lubrication. Shafts shall
be keywayed at both ends.
Blower(s) shall be licensed to bear the AMCA seal for Air Performance.
Blower(s) shall be Delhi Industries Inc., 'BIDI'
Series. www.delhi-industries.com
'DPL' Series Plenum Fan
Plenum Fan
shall be Backward Inclined (BI) suitable for AMCA Class I operation.
Wheels shall be SWSI and constructed of heavy gauge steel, (aluminum for
30”, 33”, 36”), and dynamically balanced in 2 planes. Bearings shall be
self-aligning, pillow block, ball bearing with provision for re-lubrication and
rated for a minimum L50 (average) life of 200,000 hours. Frame and
bearing support shall be constructed of heavy gauge welded angle iron.
Plenum Fan(s) shall be
licensed to bear the AMCA seal for Air Performance.
Motor shall be continuous duty, permanently lubricated, ball bearing with a 1.15
service factor. Electrical characteristics and enclosure per schedule. Drives
are to be selected for 150% of driven horsepower. Blower pulleys shall be fixed,
machined, cast iron. Blower pulleys shall be cast iron, variable speed.
(Optional): - Sliding base
motor platform
Plenum Fan(s) shall be Delhi Industries Inc., 'DPL' Series.
www.delhi-industries.com
|